Skip to content

ASHRAE 62.1

HVAKR implements ASHRAE Standard 62.1 - Ventilation for Acceptable Indoor Air Quality using the Ventilation Rate Procedure.

ASHRAE 62.1 establishes minimum ventilation rates to maintain acceptable indoor air quality:

  • Dilute contaminants
  • Provide oxygen
  • Control odors

Applies to:

  • Commercial buildings
  • Institutional buildings
  • High-rise residential (4+ stories)

For each breathing zone:

Vbz = Rp × Pz + Ra × Az

Where:

  • Vbz = Breathing zone outdoor airflow
  • Rp = Outdoor air per person
  • Pz = Zone population
  • Ra = Outdoor air per area
  • Az = Zone floor area

Adjust for distribution effectiveness:

Voz = Vbz / Ez

Where:

  • Voz = Zone outdoor airflow
  • Ez = Zone air distribution effectiveness

Each system’s outdoor air requirement follows the central unit’s Outside Air method, set in System Design > Configuration:

  • Sum of Spaces — HVAKR sums the zone outdoor airflows across the spaces the system serves:

    Vot = Σ Voz
  • Multi-Zone — HVAKR applies the ASHRAE 62.1 multi-zone equation. It divides the uncorrected outdoor air intake Vou (which applies the occupancy diversity D to the people component) by a system ventilation efficiency Ev, so the corrected intake can exceed the simple sum:

    Vou = D × Σ(Rp × Pz) + Σ(Ra × Az) + Σ Vach + Σ Vcust
    Vot = Vou / Ev

    Ev defaults to 0.75 and drops to 0.88 × D + 0.22 when occupancy diversity falls below 0.6. Each space is counted once — through its breathing-zone rate (Rp, Ra), an air-change minimum (Vach) where air changes govern, or a space-level custom requirement (Vcust) — so the three sums cover disjoint sets of spaces.

Where:

  • Vot = System outdoor airflow

See Ventilation for the full system-outdoor-air treatment, including the fixed-fraction Percent and Custom methods.

HVAKR includes all rates from Table 6.2.2.1:

Space Type Rp (CFM/person) Ra (CFM/ft²)
Office 5 0.06
Conference 5 0.06
Classroom (9+) 10 0.12
Retail 7.5 0.12
Restaurant 7.5 0.18
Gym 20 0.18

When occupancy isn’t specified, use Table 6.2.2.1 defaults.

Ez values based on supply configuration:

Configuration Ez
Ceiling supply, ceiling return 1.0
Ceiling supply, floor return 1.0
Floor supply, ceiling return 1.2
Floor supply, floor return 1.0
Stratified/displacement systems with high ceiling return 1.2–1.5
Personalized ventilation systems 1.2–1.5

Most common configuration:

  • Supply air from ceiling
  • Good mixing assumed
  • Ez = 1.0

Minimum exhaust for specific spaces:

Space Exhaust Rate
Restroom 50 CFM/fixture
Locker room 0.5 CFM/ft²
Kitchen (commercial) Per equipment

Exhaust can be satisfied by:

  • Direct outdoor air
  • Transfer from adjacent spaces

HVAKR automatically:

  • Applies rates from space types
  • Calculates zone and system requirements
  • Checks compliance