Ventilation
HVAKR calculates outdoor air requirements per ASHRAE Standard 62.1 - Ventilation for Acceptable Indoor Air Quality. This ensures adequate fresh air for occupant health and comfort.
ASHRAE 62.1 Method
Section titled “ASHRAE 62.1 Method”The Ventilation Rate Procedure calculates outdoor air based on:
- Occupancy (people-based component)
- Floor area (area-based component)
- Zone air distribution effectiveness
Breathing Zone Outdoor Air
Section titled “Breathing Zone Outdoor Air”The outdoor airflow required at the breathing zone:
People Component (Rp)
Section titled “People Component (Rp)”Outdoor air per person from ASHRAE 62.1 Table 6.2.2.1:
- Office space: 5 CFM/person
- Conference room: 5 CFM/person
- Classroom: 10 CFM/person
- Gym: 20 CFM/person
Area Component (Ra)
Section titled “Area Component (Ra)”Outdoor air per unit floor area:
- Office space: 0.06 CFM/ft²
- Conference room: 0.06 CFM/ft²
- Classroom: 0.12 CFM/ft²
- Retail: 0.12 CFM/ft²
Breathing Zone Calculation
Section titled “Breathing Zone Calculation”Vbz = Rp × Pz + Ra × AzWhere:
- Vbz = Breathing zone outdoor airflow
- Pz = Zone population (design occupancy)
- Az = Zone floor area
Zone Outdoor Air
Section titled “Zone Outdoor Air”Adjust for air distribution effectiveness:
Zone Air Distribution Effectiveness (Ez)
Section titled “Zone Air Distribution Effectiveness (Ez)”How effectively outdoor air reaches the breathing zone:
- Ceiling supply, ceiling return: Ez = 1.0
- Ceiling supply, floor return: Ez = 1.0
- Floor supply, ceiling return: Ez = 1.2 (improved)
- Floor supply, floor return: Ez = 1.0
- Stratified/displacement or personalized ventilation: Ez can exceed 1.0, up to 1.5 for eligible ASHRAE 62.1 configurations
Zone Outdoor Airflow
Section titled “Zone Outdoor Airflow”Voz = Vbz / EzSystem Outdoor Air
Section titled “System Outdoor Air”For multi-zone systems, calculate system outdoor air:
Zone Outdoor Air Fraction
Section titled “Zone Outdoor Air Fraction”The ratio of outdoor air to supply air for each zone:
Zp = Voz / VpzWhere Vpz is the zone primary airflow.
System Outdoor Airflow
Section titled “System Outdoor Airflow”HVAKR’s ventilation calculation totals each member space’s zone outdoor airflow (Voz) across the spaces the system serves, computed independently for cooling and heating with the larger governing:
Vot = Σ VozThe outdoor air the unit actually draws is set by the central unit’s Outside Air method in System Design > Configuration:
-
Sum of Spaces — the intake is the reported
Σ Vozdirectly. -
Multi-Zone — HVAKR applies the ASHRAE 62.1 multi-zone equation, dividing the uncorrected outdoor air intake
Vou(which applies the occupancy diversityDto the people component) by a system ventilation efficiencyEv, so the corrected intake can exceed the simple sum:Vou = D × Σ(Rp × Pz) + Σ(Ra × Az) + Σ Vach + Σ VcustVot = Vou / EvEach space is counted once — through its breathing-zone rate (
Rp,Ra), an air-change minimum (Vach) where air changes govern, or a space-level custom requirement (Vcust) — so the three sums cover disjoint sets of spaces.Evdefaults to0.75and drops to0.88 × D + 0.22when occupancy diversity falls below0.6. HVAKR derivesEvfrom occupancy diversity rather than the full ASHRAE 62.1 critical-zone (Appendix A) efficiency procedure.
The Percent and Custom methods instead set the intake to a fixed fraction of supply air or a fixed flow rate, bypassing the ventilation-based calculation.
VAV System Considerations
Section titled “VAV System Considerations”For VAV systems, ventilation varies with airflow:
Minimum Airflow
Section titled “Minimum Airflow”Zones must maintain minimum airflow for ventilation:
- At minimum, outdoor air fraction increases
- May require outdoor air reset
Exhaust Air Requirements
Section titled “Exhaust Air Requirements”Some spaces require exhaust per 62.1:
Exhaust Rates
Section titled “Exhaust Rates”From Table 6.5:
- Restrooms: 50-70 CFM per fixture
- Kitchens: Varies by equipment
- Laboratories: Per hood requirements
Transfer Air
Section titled “Transfer Air”Exhaust can be satisfied by:
- Direct outdoor air
- Transfer air from adjacent spaces
- Combination
Results Display
Section titled “Results Display”Zone Ventilation Summary
Section titled “Zone Ventilation Summary”For each zone:
- Breathing zone outdoor air (Vbz)
- Zone outdoor air (Voz)
- Zone outdoor air fraction (Zp)
System Ventilation Summary
Section titled “System Ventilation Summary”For each system:
- Total outdoor air (Vot)
- Outdoor air fraction
Compliance Verification
Section titled “Compliance Verification”Verify ASHRAE 62.1 compliance:
- Check that all spaces have appropriate space types
- Verify occupancy matches design intent
- Confirm zone OA fractions are achievable
- Review system-level OA requirements