Duct Layout
The Layout pane is where you design the duct distribution system, including routing, sizing, and component selection.
Duct Routing
Section titled “Duct Routing”Creating Duct Runs
Section titled “Creating Duct Runs”Draw duct runs on the floor plan:
- Select the duct tool
- Click to place duct segments
- Connect to terminals and registers
- Close loops where needed
Duct Types
Section titled “Duct Types”Select the appropriate duct type:
- Supply duct - From AHU to terminals
- Return duct - From spaces back to AHU
- Exhaust duct - From spaces to exhaust fan
- Outdoor air - From intake to AHU
Routing Considerations
Section titled “Routing Considerations”Plan duct routes to:
- Minimize total length
- Avoid obstructions
- Allow for insulation and access
- Fit within available plenum space
Duct Sizing
Section titled “Duct Sizing”Sizing Methods
Section titled “Sizing Methods”HVAKR supports multiple sizing methods:
Velocity Method
Section titled “Velocity Method”Size ducts for a target velocity:
- Higher velocity = smaller ducts
- Lower velocity = quieter system
- Typical: 1500-2000 FPM main, 800-1200 FPM branch
Equal Friction
Section titled “Equal Friction”Size for constant friction rate:
- Typical: 0.08-0.10 in. wg per 100 ft
- Self-balancing in symmetric layouts
- May result in high velocity in mains
Static Regain
Section titled “Static Regain”Size to maintain static pressure:
- Pressure regained at branches
- Self-balancing
- More complex calculations
Automatic Sizing
Section titled “Automatic Sizing”HVAKR automatically sizes ducts:
- Set the sizing method and parameters
- Run the sizing calculation
- Review and adjust as needed
Fittings and Transitions
Section titled “Fittings and Transitions”Fitting Types
Section titled “Fitting Types”Select fittings for duct connections:
- Elbows - 90°, 45°, or radius
- Tees - Branch takeoffs
- Transitions - Size changes
- Offsets - Vertical or horizontal shifts
Fitting Loss Coefficients
Section titled “Fitting Loss Coefficients”Fittings add pressure loss:
- ASHRAE fitting loss coefficients
- Based on fitting geometry
- Included in total pressure calculation
Reducing Losses
Section titled “Reducing Losses”Minimize fitting losses:
- Use larger radius elbows
- Avoid abrupt transitions
- Use turning vanes where needed
Pressure Calculations
Section titled “Pressure Calculations”Pressure Graph
Section titled “Pressure Graph”View the pressure profile through the system:
- Static pressure at each point
- Velocity pressure
- Total pressure
Critical Path
Section titled “Critical Path”Identify the critical path:
- Highest pressure drop path
- Determines fan sizing
- Other paths need balancing
Fan Sizing
Section titled “Fan Sizing”The fan must overcome:
- Total duct pressure drop
- Terminal unit pressure drop
- Filter pressure drop
- Coil pressure drop
3D Visualization
Section titled “3D Visualization”View the duct layout in 3D:
- Rotate and zoom the model
- Check for interferences
- Verify routing and sizing
Duct Schedule
Section titled “Duct Schedule”Generate a duct schedule report:
- Duct sizes by segment
- Fitting schedule
- Insulation requirements
- Total duct area
Best Practices
Section titled “Best Practices”- Route before sizing - Establish routing first
- Use consistent sizing method - Don’t mix methods
- Check velocities - Stay within acceptable ranges
- Verify pressure drop - Within equipment capability
- Document routing - For construction drawings