Skip to content

Configuration

The Configuration pane is where you set up the HVAC equipment for each system. This includes central air handling units and zone terminal units.

Select the type of central equipment:

  • Air Handling Unit (AHU) - Central station with coils and fan
  • Rooftop Unit (RTU) - Packaged rooftop equipment
  • Split System - Indoor air handler with outdoor condenser
  • Make-Up Air Unit - 100% outdoor air systems

The total cooling capacity of the unit:

  • Calculated from peak system load
  • Includes safety factors
  • Accounts for ventilation load

The design temperature of air leaving the cooling coil:

  • Typically 55°F (13°C) for dehumidification
  • Higher temperatures reduce dehumidification
  • Lower temperatures increase capacity

Cooling coil parameters:

  • Entering and leaving conditions
  • Face velocity
  • Rows and fin spacing

Select the heating source:

  • Hot water coil
  • Electric resistance
  • Gas furnace
  • Heat pump

The total heating capacity:

  • Calculated from peak heating load
  • May include morning warm-up
  • Accounts for infiltration and ventilation

Supply airflow and pressure:

  • Design CFM based on peak load
  • External static pressure
  • Fan type and efficiency

For systems with return fans:

  • Return airflow
  • Return static pressure
  • Relief/exhaust coordination

Select the zone terminal equipment:

  • VAV Box - Variable air volume with optional reheat
  • Fan Coil Unit - Local fan with cooling/heating coil
  • Constant Volume - Fixed airflow terminals

The lowest airflow setting:

  • Percentage of peak airflow
  • Or fixed CFM value
  • Must meet ventilation requirements

For heating in VAV systems:

  • Hot water reheat
  • Electric reheat
  • Dual-duct heating

How terminal units are sized:

  • Peak zone load
  • Minimum ventilation
  • Maximum velocity limits

The required outdoor air for ventilation:

  • Calculated per ASHRAE 62.1
  • Sum of zone requirements
  • Adjusted for system efficiency

For free cooling with outdoor air:

  • Dry-bulb economizer
  • Enthalpy economizer
  • Differential controls

Heat or energy recovery from exhaust:

  • Sensible heat recovery
  • Enthalpy recovery
  • Effectiveness and pressure drop

How the system maintains setpoint:

  • Cooling/heating sequencing
  • Reset schedules
  • Economizer integration

For VAV systems:

  • Static pressure setpoint
  • Pressure reset strategies
  • Critical zone tracking

After configuration, verify:

  • Capacity meets peak loads
  • Airflow is adequate for ventilation
  • Pressure drop is within limits
  • Equipment selections are realistic