Skip to content

Air Balancing

Air balancing ensures that each zone receives the correct airflow for cooling, heating, and ventilation. This section covers airflow distribution and register selection.

Each zone requires airflow based on:

  • Peak cooling airflow - To meet peak sensible load
  • Minimum ventilation - ASHRAE 62.1 requirements
  • Heating airflow - For systems with air-side heating

Total system airflow is the sum of zone airflows, adjusted for:

  • Diversity (zones don’t all peak simultaneously)
  • Safety factors
  • Duct leakage allowance

Select supply air outlets for each zone:

  • Ceiling diffusers - Square, round, or linear
  • Sidewall registers - For perimeter heating
  • Floor registers - For underfloor systems
  • Throw - Distance air travels from the register
  • Spread - Width of the air pattern
  • Noise level - NC rating at design airflow
  • Pressure drop - Static pressure loss

Size registers based on:

  • Zone airflow requirement
  • Maximum face velocity (typically 500-700 FPM)
  • Throw requirement for the space
  • Acceptable noise level

Configure return air for each zone:

  • Return grille sizing
  • Return plenum vs. ducted return
  • Transfer air between spaces

For spaces with exhaust requirements:

  • Exhaust airflow (from space type)
  • Exhaust fan selection
  • Make-up air requirements

Verify air balance for each zone:

  • Supply = Return + Exhaust + Transfer
  • Positive pressure for critical spaces
  • Negative pressure for restrooms, kitchens

HVAKR calculates the pressure drop through the duct system:

  • Duct friction losses
  • Fitting losses
  • Terminal unit losses
  • Register losses

The path with the highest pressure drop:

  • Determines fan static pressure
  • Used for duct sizing
  • Identifies balancing challenges

For paths shorter than critical:

  • Dampers add pressure drop
  • Balance to match critical path
  • Shown on duct layout

ASHRAE 62.1 ventilation for each zone:

  • Breathing zone outdoor air (Vbz)
  • Zone air distribution effectiveness (Ez)
  • Zone outdoor air fraction (Voz)

Total system outdoor air:

  • Sum of zone requirements
  • Adjusted for system efficiency
  • Multiple spaces equation if applicable

Check that each zone receives adequate outdoor air:

  • Primary air at minimum airflow
  • System outdoor air fraction
  • Critical zone requirements
  1. Size registers for throw - Match throw to room dimensions
  2. Check noise levels - Verify NC ratings are acceptable
  3. Balance return and exhaust - Account for all air leaving the zone
  4. Verify ventilation - Ensure ASHRAE 62.1 compliance
  5. Document the critical path - For commissioning reference