Skip to content

Heating Loads

Heating load represents the rate at which heat must be added to maintain indoor design conditions during peak heating conditions.

HVAKR uses steady-state calculation for heating loads:

  • Based on design heating temperature (99.6% condition)
  • No solar credit (conservative, assumes nighttime peak)
  • No internal gains credit (unoccupied condition)
  • Results in maximum required heating capacity

Heat loss through the building envelope:

  • Indoor-to-outdoor temperature difference
  • Wall U-value and area
  • No solar effect (nighttime condition)
  • Similar to walls
  • Higher U-value increases loss
  • Significant for top floors
  • Conductive heat loss
  • Higher U-value than walls
  • No solar credit
  • Slab-on-grade uses perimeter method
  • Basement uses ground temperature
  • Usually smaller than other components
  • Conductive heat loss
  • Higher U-value than walls
  • Include all exterior doors

Heat to warm cold outdoor air leaking in:

  • Based on envelope tightness
  • Increases with wind speed
  • May be significant in older buildings

Heat to warm outdoor ventilation air:

  • Based on minimum outdoor air requirement
  • Outdoor-to-indoor temperature difference
  • No latent component (typically)

For conservative sizing, heating loads exclude:

  • Peak heating often occurs before sunrise
  • Cloudy conditions are possible
  • Results in reliable capacity
  • Building may be unoccupied
  • Morning warm-up requires extra capacity
  • Results in quick recovery

The 99.6% heating design temperature:

  • Temperature exceeded 99.6% of hours
  • Only 35 hours per year below this value
  • Conservative for equipment sizing

Typical heating setpoint:

  • 68-72°F (20-22°C) occupied
  • Lower for setback periods
  • May vary by space type

Heating loads peak when:

  • Outdoor temperature is at design minimum
  • No solar gain (night or cloudy)
  • Building is unoccupied (no internal gains)

Additional capacity for morning recovery:

  • Building cooled down overnight
  • Need to reach setpoint before occupancy
  • May increase heating load by 20-30%

View heating loads for each space:

  • Total heating load
  • Load component breakdown
  • Heat loss per envelope element

Aggregate heating loads by system:

  • Sum of zone loads
  • No diversity applied (all zones heat simultaneously)
  1. Check envelope areas - Verify wall and window areas
  2. Review U-values - Compare to specifications
  3. Consider infiltration - May be significant
  4. Compare to benchmarks - Typical 15-25 BTU/h per sf for offices
  5. Verify temperature difference - Design delta-T is correct